Changes to Master Controller Command 0x23
These are changes that improved the stability of the ATG readings – its very important to understand these settings they would need to be tuned to different Tank sizes and rates of flow in and out of the tank.
Device Parameter Settings . Polling_Time = Upper nibble is sample times until report an event
Device Parameter Settings . Polling_Time = Lower nibble is polling ATG interval in seconds
Device Parameter Settings . Spare Control 1 = ATG_Difference_in_mm
Device Parameter Settings . Spare Control 1 * 4 = Noise level Filtering
NB: if the ATG is tracking 2mm change in level, then Noise Level Filtering would ignore readings outside a window of +- 8 (i.e. 2x4)
Device Parameter Settings . Spare Control 2 = Mean samples (1 = no mean)
Device Parameter Settings . Spare Control 3 = Quantity of wrong samples to restart the mean cycle
If there are too many readings (determined by this setting) outside the Noise Level Filtering, the process of finding a Mean restarts with new data.